More about Aerotech® AeroSpeed 1.2
Used to regulate the environment in livestock buildings, the Aerotech AeroSpeed 1.2 maintains your desired temperature in the facility by controlling the operation of ventilation and heating equipment. One stage of variable speed cooling fans can be connected to the controller, as well as two stages of either constant-speed fans or heating units. The last cooling stage can be configured as a mist cooling stage.
Features of the ST 5120:
-
Three Digit Display
- Provides a high level of accuracy, allowing you to specify a temperature to within 1/10 of a degree (in Fahrenheit or Celsius units)
-
Pilot Lights
- Indicate the state of outputs allow you to monitor the operation of the system without having to enter the building
-
Minimum Ventilation Cycle
- When ventilation is not required for cooling, the first stage fans can be operated either continuously or intermittently to reduce the level of humidity and supply oxygen to the room
-
Temperature & Minimum Ventilation Speed Curves
- Can be set to automatically change the temperature set point and minimum ventilation speed over a given period of time in accordance with your requirements by specifying a temperature curve and a minimum ventilation speed curve with up to 6 different points each
-
Choice of 5 Motor Curves
- The variation in motor speed resulting in a change in voltage will depend on the make and capacity of the motor. In order to achieve a high degree of compatibility between controller and motor, you can choose from among 5 different motor curves, to ensure the correct voltage is supplied
-
Full Speed Fan Start-Up
- To overcome the inertia of the ventilation system components and de-ice the fan blades in cold weather conditions, the controller supplies maximum voltage to the variable speed fans for 2 sec immediately following each start-up
-
4 Independent Temperature Probe Inputs
- Up to 4 temperature probes can be connected to obtain a more accurate reading of the average room temperature and a faster reaction time
-
Overload and Overvoltage Protection
- Fuses are installed at the input and outputs to protect its circuitry in the case of an overload or overvoltage
-
Computer Control
- Can be connected to a computer, making it possible to centralize the management of information and diversify control strategies
Several Models To Choose From. Features of All Models:
- Fully adjustable temperature and ventilation curves
- Variable speed outputs have optional timer option
- Minimum, maximum temperature recordings
- 12' sensor included
- 120/240 volt
- 10 amp maximum fan load
1.2 Technical Specifications:
-
Supply:
- 115/230 VAC (-18%-+8%), 60 Hz, L1 same phases as Stage 1, overload and overvoltage protection fuse F11-1A fast blow
- 12 VDC for AC back-up supply; can activate stage 2-3 and alarm if supplied with DC back-up voltage
-
Stage 1:
- Variable output, 60 Hz, 10A fan (3/4 HP/115 VAC)/(1.5 HP/230 VAC), fuse F1-15A slow blow
-
Stage 2:
- On/Off output, 115/230 VAC, 60 Hz, 30 VDC, 6A Fan, 10A Res, fuse F2-15A slow blow
-
Stage 3:
- On/Off output, 115/230 VAC, 60 Hz, 30 VDC, 6A Fan, 10A res, fuse F3-15A slow blow
-
Alarm:
- On/Off output, 115/230 VAC, 60 Hz, 30 VDC, 3A, fuse F8-3A slow blow
-
Probes:
- Low voltage (<5V), isolated from the supply. Operating range: -40° F to 120° F. Accuracy: 1.8° F between 41° F and 95° F
-
Enclosure:
- ABS, moisture and dust-tight
- The room temperature where the controller is located MUST ALWAYS REMAIN between 32° F and 104° F
Factory Settings:
Parameter | Factory Setting | Range of Values | |
---|---|---|---|
Temperature Set Point | 75° F | -40° F to 99.9° F | |
Stage 1 | Minimum Speed | 40% | 10%-100% |
Time On | 15 sec | 0-900 seconds by increments of 15 sec |
|
Time Off | 0 sec | ||
Bandwidth | 3° F | 0.5° F - 20° F | |
Stage 2 Starting Temp | 80° F | 0.5° F - 20° F from bandwidth |
|
Stage 3 Starting Temp | 82° F | 0.5° F - 20° F from Stage 2 starting temp |
|
Mist | Time On | 1 min | 0-60 min by increments of 1 min |
Time Off | 0 min | ||
Heater Off Temperature | 74.5° F | -20° - 10° F from set point |
|
Alarm | Low Temperature | 65° F | 0.5° F - 40° F from set point |
High Temperature | 87° F |
These initial parameter settings will not be retained in the controller's memory. Each new setting will replace the preceding one.
If the power supply is cut off, the last parameter settings will be retained in the memory until the power is restored.
Model | QC Part # | Mfg Part # | Variable Speed Outputs | Thermal Contacts | Cooling (only) Contact | Sensors (max) | PC Loop | Ramping Timer | Alarm Contacts |
---|---|---|---|---|---|---|---|---|---|
AeroSpeed 1.1 | 10860 | ST5110 | 1 | 1 | 9 | 4 | Yes | No | Yes |
AeroSpeed 1.2 | 10861 | ST5120 | 1 | 2 | 1 | 4 | Yes | No | Yes |
AeroSpeed 1.3 | 10862 | ST511 | 1 | 2 | 4 | 4 | Yes | No | Yes |
AeroSpeed 1.6 | 10863 | ST5124 | 1 | 2 | - | 4 | Yes | No | Yes |
AeroSpeed 2.2 | 10865 | ST5220 | 2 | 2 | 2 | 4 | Yes | No | Yes |
AeroSpeed 2.4 | 10866 | ST5222 | 2 | 2 | 2 | 5 | Yes | Yes | Yes |